Three phase two winding transformer
This section describes three phase two winding transformer
The three-phase transformer is modeled as three single-phase transformers, meaning that only magnetic coupling between windings of the same phase are taken into account. The magnetization inductance Lm can be linear or with saturation, it is modeled on the primary side of the transformer. Core losses are modeled as Rm resistance located on the primary side of the transformer. Also, it is possible to neglect Lm and Rm by selecting Lm/Rm neglected in the Core model property. Finally, Hysteresis can also be simulated for slower dynamics. For more information, please refer to the Core model section.
Schematic symbol and input parameters for the three phase two winding transformer block are given in Table 1.
component | component dialog window | component parameters |
---|---|---|
Three phase two winding transformer |
|
|
|
||
|
- short circuit test – exciting a set of three-phase windings while the other set of windings is short circuited
- open circuit test – exciting a set of three-phase windings while the other set of windings is open circuited
Measurement results obtained from these tests and other information given on the transformer’s nameplate provide the necessary data for transformer characterization and modeling.
Winding excitation in the tests is three-phase positive sequence voltage. In addition to that, when characterizing a transformer and making a transformer model that includes mutual inductances between phases, it is necessary to perform the same tests, but with excitation being three-phase zero sequence voltage.
Parameters of the equivalent circuit are calculated as follows. During the short circuit test, the magnetization branch is considered shorted by the short circuited winding. So, primary side short circuit impedance is obtained:
Primary side short circuit resistance is obtained:
Primary side short circuit inductance:
Primary and secondary side resistances and short circuit inductances are calculated using:
From the positive sequence open circuit test results, it is obtained:
Variables description:
Sn - nominal power of transformer
V1nph - primary side nominal phase voltage
fn - nominal frequency
N2/N1 - transfer ration
uscd - short circuit voltage (sc) – positive sequence (d)
Zscd - short circuit impedance (sc) – positive sequence (d)
Pscd - short circuit active power (sc) – positive sequence (d)
Rsc - short circuit resistance (sc)
Lscd - short circuit inductance (sc) – positive sequence (d)
R1 - resistance on primary side
R2 - resistance on secondary side
L1d - leakage inductance on primary side – positive sequence (d)
L2d - leakage inductance on secondary side – positive sequence (d)
iocd - open circuit (oc) excitation current – positive sequence (d)
i1nph - nominal phase current
Pocd - open circuit (oc) losses– positive sequence (d)
RFed (Rm) - resistance representing the core losses under nominal voltage – positive sequence (d)
iFed - current due to core losses under nominal voltage – positive sequence (d)
imd - magnetizing current – positive sequence (d)
Lmd - magnetizing inductance – positive sequence (d)
A schematic block diagram of the three-phase two-winding transformer block with the corresponding component arrangement and naming is shown in Figure 1.
It should be noted that terminals N1 and N2 can be connected with the rest of the circuit in schematic editor only if the corresponding side is wye (Y) connected.
Embedded coupling
There are two possible options for embedded coupling in the single phase two winding transformer, Ideal Transformer based coupling and TLM coupling.
If Embedded coupling is Ideal Transformer, Ideal Transformer based coupling will be placed between two windings of transformer.
In Figure 2 is given a visual representation of division of transformer's equivalent circuit in the case where Embedded coupling is set to Ideal Transformer.
If Embedded coupling is set to TLM, secondary winding inductor in the each phase will be replaced with TLM coupling component. Inductance will be divided between coupling and embedded inductors (inductors will be hidden in the TLM). TLM to embedded inductors ratio can be determined by compiler, but also it can be specified explicitly. If Automatic option is selected, ratio will be determined by discretization method. If Manual option is selected, ratio can be explicitly set to meet user requirements. For more information on TLM couplings please refer to Core couplings - TLM.
In Figure 3 is given a schematic representation of transformer's equivalent circuit when Embedded coupling is set to TLM.
Analog output signals from three phase two winding transformer
Internal variables of the transformer are available for observation at the analog outputs. Names of the variables available for observation have extensions _a, _b and _c added to their names. These extensions correspond to variables of sub circuits of phases a, b and c, respectively.
Analog output variable name | Description |
---|---|
Lm_a_name | Current of magnetizing inductance in phase A |
Lm_b_name | Current of magnetizing inductance in phase B |
Lm_c_name | Current of magnetizing inductance in phase C |
L1_a_name | Current of phase A leakage inductance on primary side |
L1_b_name | Current of phase B leakage inductance on primary side |
L1_c_name | Current of phase C leakage inductance on primary side |
L2_a_name | Current of phase A leakage inductance on secondary side |
L2_b_name | Current of phase B leakage inductance on secondary side |
L2_c_name | Current of phase C leakage inductance on secondary side |